XGN15-12 box-type stationary metal enclosed high voltage switchgear

Features
  • The unit modules can be combined and expanded freely without the need of charging and discharging, so as to facilitate scheme combination and high voltage metering design.
  • The extensible busbar is provided with a pluggable silicon rubber connector which can realize fully-insulating and shielding and ensure the conduction reliability.
  • It is convenient to install cable due to the front plugging.
  • Detachable, fast to recover and convenient to install during overhaul.
  • New semiconductor material is used as the shielding layer to prevent appearance from humidity, condensation, dust and dirt.
Applicable place
  • TAC 50HZ 12KV power system and used for the distribution system and box-type substation such as urban residential area distribution, small secondary distribution station, small switching station, industrial and mining enterprises, high-rise buildings, residential communities, hospitals, stadiums and parks.

Product Details

DOWNLOAD



  • Model Description


  • Features
    • The unit modules can be combined and expanded freely without the need of charging and discharging, so as to facilitate scheme combination and high voltage metering design.
    • The extensible busbar is provided with a pluggable silicon rubber connector which can realize fully-insulating and shielding and ensure the conduction reliability.
    • It is convenient to install cable due to the front plugging.
    • Detachable, fast to recover and convenient to install during overhaul.
    • New semiconductor material is used as the shielding layer to prevent appearance from humidity, condensation, dust and dirt.
  • Conditions of Use
    • Altitude: ≤1,000m;
    • Ambient temperature: +45℃- -5℃;
    • Surrounding relative humidity: daily average value: ≤95%; monthly average value: ≤90%;
    • There is no obvious dust, smoke, corrosive or combustible gas, vapor or salt pollution in surrounding air; The seismic intensity is ≤8°.
    • Note: when the using environment conditions exceed this condition, please consult with the manufacturer.

  • Technical Parameters



    S/N

    Name

    Unit

    Technical parameters

    Load switch cabinet

    Load switch fuse combination electrical cabinet

    1

    Rated voltage

    kV

    12

    2

    Rated frequency

    Hz

    50

    3

    Rated current

    A

    630

    125 (max)

    4

    Rated insulation level

    1min withstand voltage with rated power frequency

    kV

    42

    Rated lightning impulse withstand voltage

    kV

    75

    5

    Rated short-circuit breaking current

    kA

    31.5

    6

    Rated short-circuit making current

    kA

    50

    80

    7

    Rated short time withstand current and duration

    kA/s

    20/3

    8

    Rated peak withstand current

    kA

    50

    9

    Transfer current

    A

    1700

    10

    Protection grade

    IP3X/IP4X



  • Leave A Message

    Name*

    Phone*

    Mailbox*

    Content*

    在线客服